| Self-monitoring and fail-safe control unit for the monitoring of gas, oil and coal flames with DURAG UV, UV+IR or IR- flame sensors, primarily in multiple-burner furnaces | |
|
Features |
|
|
Suitable for intermittent operation, continuous operation and 72-hour operation as per TRD 604 |
|
|
Optional parallel operation of two flame sensors in any combination: UV/UV, UV/IR or IR/IR |
|
|
Three different settings supported for various modes (e.g. dependent on fuel or combustion technology), automatic activation by burner management system |
|
|
Plain text display |
|
|
Applications |
|
| Power stations | |
|
Chemical industry |
|
|
Refineries |
|
|
Cement plants |
|
|
Waste incinerators |
|
|
Steam generators |
|
|
Heating plants |
|
|
Operational mode |
intermittent operation, continuous operation and 72-hour operation without permanent supervision |
|
Safety |
self-monitoring and fail-safe in conjunction with a control unit/burner control |
|
Power supply |
24/48 VAC or VDC, 115/230 VAC |
|
Protection |
IP00 |
|
Flame relay |
1x switch-over contact, 230 VAC, 2A |
|
Status relay |
1x switch-over contact, 230 VAC, 2A |
|
Switching threshold |
00...99 |
|
Safety time |
1 ... 5,5s |
|
Pre-configurable combinations of switching threshold and safety time |
3 |
|
Flame sensor connection |
1 or 2 (parallel) |
|
Display |
Alphanumerische LCD-Display |
|
Flame intensity |
0/4...20 mA |
|
Flame signal |
0/4...20mA |
|
Perm. ambient temperature |
-20...+60°C |
|
Dimensions |
19" plug-in module, 3 RU, 21 HP |
|
Weight |
approx. 1 kg |
|
Self-monitoring and fail-safe control unit for the monitoring of gas, oil and coal flames with DURAG UV, UV+IR or IR flame sensors, primarily in single burner furnaces |
|
|
Features |
|
|
suitable for intermittent operation, continuous operation and 72-hour operation according to TRD 604 |
|
|
LED display |
|
|
installation on DIN-rail |
|
|
Applications |
|
| Power stations | |
|
Chemical industry |
|
|
Refineries |
|
|
Cement plants |
|
|
Waste incinerators |
|
|
Steam generators |
|
|
Heating plants |
|
|
Operational mode |
intermittent operation, continuous operation and 72-hour operation without permanent supervision |
|
Safety |
self-monitoring and fail-safe in conjunction with a control unit/burner control |
|
Power supply |
24 VDC |
|
Protection |
IP20 |
|
Flame relay |
1x NO contact, 230 VAC, 2A |
|
Status relay |
1x NO contact, 230 VAC, 2A |
|
Installation |
TS 35 DIN-rail |
|
Safety time |
1 s |
|
Configurable switching thresholds |
1 |
|
Switching thresholds |
0...9 |
|
flame sensor |
1 |
|
Display |
LED |
|
Flame intensity |
0/4...20 mA |
|
Perm. ambient temperature |
-20...+60°C |
|
Dimensions |
100 x 75 x 118 mm (WxHxD) |
|
Weight |
approx. 0.45 kg |