Self-monitoring and fail-safe burner control for the control of gas and oil burners as well as combined gas/oil burners of any capacity |
|
|
Features |
|
|
Controling and monitoring of gas and oil burners of any capacity |
|
|
Suitable for intermittent operation, continuous operation and 72-hour operation according to TRD 604 |
|
|
Integrated gas valve monitoring system |
|
|
Separate outputs for control of gas and oil fuel valves |
|
|
Quick fuel change "on the fly" without burner shut down |
|
| Adjustable Pre-purge timer | |
| Integrated flame monitor | |
| Input for external flame monitor | |
| Data interface | |
|
Applications |
|
|
Chemical industry |
|
|
Refineries |
|
|
Cement plants |
|
|
Waste incinerators |
|
|
Steam generators |
|
|
Heating plants |
|
|
Operational mode |
intermittent operation, continuous operation and 72-hour operation without permanent supervision |
|
Safety |
self-monitoring and fail-safe |
|
Power supply |
115/230 VAC , 50 / 60 Hz |
|
Protection |
IP20 |
|
Installation |
DIN-rail TS 35 |
|
Switching treshold |
0…9 |
|
Pre-purge |
30 s…20 min |
|
Flame sensor |
1, 2 parallel or external flame monitor |
|
Display |
LED |
|
Flame intensity |
0/4…20 mA |
|
Datenausgang |
to D-AM 150 / D-ZS 087-20 |
|
Dimensions |
170 x 130 x 114 mm (LxWxH) |
|
Weight |
approx. 1.5 kg |
|
Self-monitoring and fail-safe burner control for the control of gas and oil burners as well as combined gas/oil burners of any capacity |
|
|
Features |
|
|
Controlling and monitoring of gas and oil burners of any capacity |
|
|
Suitable for intermittent operation (D-GF 55-10) and continuous operation (D-GF 55-20) |
|
|
Integrated ionisation flame monitor |
|
|
Input for external flame monitor |
|
|
Applications |
|
|
Chemical industry |
|
|
Refineries |
|
|
Cement plants |
|
|
Waste incinerators |
|
|
Steam generators |
|
|
Heating plants |
|
|
Operational mode |
D-GF 55-10: intermittent operation |
|
Safety |
self-monitoring and fail-safe |
|
Power supply |
115 / 230 VAC, 50 / 60 Hz |
|
Protection |
IP 20 |
|
Perm. ambient temperature |
-20…+60°C |
|
flame sensor |
- ionisation electrode |
|
Installation |
DIN-rail TS 35 |
|
Start-up safety time |
3 s, 5 s or 10 s |
|
Operation safety time |
1 s, 3 s or 5 s |
|
Flame intensity |
0…50 µA |
|
Display |
LED |
|
Dimensions |
100 x 75 x 118 mm (LxWxH) |
|
Weight |
approx. 0.7 kg |
|
D-LE 55 UL-CG flame sensor |
|
|
Spectral sensitivity |
190 – 270 nm |
|
Protection |
IP 67 |
|
Perm. ambient temperature |
-20…+60°C |
|
Weight |
approx. 0.35 kg |
|
Installation |
G 1“ or G ½“ |